Meets ANSI Z358.1-2004
Reliable liquid-filled thermostat with 10 year warranty
Checkstops on inlets
Adjustable set point within temperature range
Accurate temperature control to within ±3ΊF
Built-in cold water bypass, assuring cold flow
Positive shut-off of hot supply when cold supply is lost
Easy installation and serviceability
Dirt and lime resistant
Dial thermometer
Factory assembled and tested
Universal mounting capability
Specification
Emergency fixture water mixing valve shall consist of liquid-filled thermal motor and a piston control mechanism with positive shut off of hot water when cold water supply is lost to prevent scalding. In addition, the valve shall allow cold flow in the event of loss or interruption of the hot water supply or thermostat failure. The valve shall control outlet temperature and will be suitable for eyewash or eye/face wash applications. Temperature adjustment will be vandal resistant